Name:Clamp-on Ultrasonic Flow Meter
Model:LRF-3300SW
Size:254*230*64mm
General Introduction:
LRF-3300S is a wall-mount, clamp- on type ultrasonic flowmeter which use the transfer time technology. Clamp on type ultrasonic flowmeter is easy to install and no need to cut off the pipe, that saves you lots of troubles and cost. At the same time
LRF-3300S has our unique calculate software to ensure the high accuracy and low velocity response. LRF-3300S could add the RTD model and temperature sensor become an energy meter to monitoring the energy use, help to save the energy.
Selection of parameter:
Model | Transmitter |
LRF-3300S | Ultrasonic flowmeter
Wall mount
Flow range :±0.01m/s ~ ±12m/s
Accuracy :±0.5% of the measure value
Repeatability:0.1% of the measure value
Display:240*128 backlit LCD
Power supply:90-250VAC,48-63Hz or 10-36VDC
Output:4-20Ma,OCT,Relay
Communication :RS232/RS485,Modbus
|
Code | Output |
1 | OCT,Relay,RS232/485,4-20mA |
2 | OCT,Relay,RS232/485,4-20mA,RTD |
Code | Transducer |
TT02 | Clamp-on, IP68,Operating temperature: -40℉ ~ + 176℉(-40℃ ~ +80℃)(Standard) |
TT03 | Clamp-on, IP68,Operating temperature: 32℉ ~ + 266℉(0℃ ~ +130℃)(High Temp) |
XXX | Transducer cable length |
030 | Standard length 30ft (9m) |
XXX | Max length to 1000ft (300m) |
Code | Temperature sensor |
PT1000 | PT1000 temperature sensor |
Transmitter:
Transducer:
size:
weight:
weight:
Installation diagram:
Performance | |
Flow range | ±0.09ft/s ~ ±40ft/s (±0.03m/s ~ ±12m/s) |
Accuracy | ±0.5% of reading (for ±1.5ft/s~±40ft/s) |
Repeatability | 0.1% of measured value |
Pipe size | 1"to 200" (25mm to 5000mm). Pipe size under 1" is an option |
Linearity | ±0.5% |
Function | |
Outputs | Analog output: 4~20mA, max load 750 Ω.
Pulse output: 0~9999Hz, OCT, (min. and max. frequency is
adjustable)
Relay output: SPST, max 1Hz,(1A@125VAC or 2A@30VDC)
|
Communication | RS232 & RS485 |
Memory | TF card (Max 32G) |
Power supply | 90 to 245 VAC, 48 to 63 Hz. Or 10 to 36VDC |
Display | 240*128 back lit LCD |
Temperature | Transmitter: -40℉~ 140℉(- 40℃ ~ 60℃ ).
Transducer: -40℉~ 176 ℉(- 40 ℃ ~ 80 ℃(Standard)
Transducer: 32℉~ 356 ℉( -0 ℃ ~ 180 ℃(High Temp type))
|
Humidity | Up to 99% RH,non-condensing |
physical | |
Transmitter | IP65 |
Transducer | IP68
Encapsulated design
Double-shielded transducer cable
Standard/maximum cable length:30ft/1000ft(9m/300m)
|